Site map      Email  

Marine Lightning Protection

If you have any additional questions that should appear here, please send us an email.

Frequently asked questions about our products

We specialize in the manufacture of the following items:

·         SiedarcTM - spark-promoting grounding electrodes embedded in Marelon through-hulls;

·         HStripTM – 0.5 ft2 tinned solid copper grounding strip.

As a service we also address some commonly held misconceptions and more general questions that have little to do with our products.

SiedarcTM

Question

Answer

Has any testing been done?

Yes, with promising results

Can the electrode survive 100% of all lightning currents?

No, but 99+% is no problem

Why is the electrode/cable connection over engineered?

This is the weak link

Do current or pending standards allow for sparking grounding electrodes?

Standards are in flux

Q.  Has any testing been done?

A.  Yes.  We (Ewen Thomson, Ken Elder and Richard Cohen) conducted some tests with a 10 kV voltage source using KENNICK Inc.'s generator.  One of the experiments was as follows.  An electrode was placed with its tip about 4 mm above the surface of sea water from the Gulf of Mexico as shown in the photo on the left.  The galvanized steel water tank was 24" in diameter.  The rings on the bottom of the tank are spaced at about 1" intervals to give an idea of scale.

    
Photo by Ken Elder, KENNICK Inc

The picture on the right shows the sparking extent for one test.  Note that the ~15" diameter of the sparks is about 100x larger than what would be expected between flat plates.  A particularly interesting feature of the sparks is their occurrence in the air just above the water surface. Similar tests done with immersed electrodes resulted in entirely different phenomena - a glow discharge rather than spark formation occurring over a much smaller distance (~ 1/2" diameter).

Despite the low voltage of these experiments, the observed mechanism of spark channel formation in the air just above the water surface is consistent with other scientists' interpretation of much larger sparks and actual lightning.  One explanation is that the sparks attach to charges on the surface of the water.  This observation is the reason why we suggest that our SiedarcTM electrodes should be installed just above the water surface.

Q.  Can the electrode survive a 100% lightning current?

A.  No lightning conductor can withstand 100% of all lightning strikes.  The main problem is overheating from long continuing currents, that occur in about half of all lightnings and are responsible for fire ignition.  Physically, there is about a 10V voltage across the electrode-discharge interface.  Hence for a charge of say 10 C, the electrode tip is subject to 100 J of heating.  However, once the tip starts melting, no further temperature increase is possible since the metal vapor disperses.  Without going into further proprietary details, we pay careful attention to these factors in the design of our electrodes.  As a starting point, we adopted an engineering approach and designed each electrode to the same specification as that advocated by NFPA 780 for an air terminal for a Class II lightning– a 1/2" diameter solid copper rod with a shaped tip.  Tin electroplating is added for superior corrosion resistance and compatibility with connectors inside the boat. 

Q.  Why is the electrode/cable connection over engineered?

A   In our experience, the weakest link of any lightning protection system is each connection.  To make the best possible connection to each SiedarcTM electrode we get each one rotary swaged using the same process as that used for standing rigging.  Were it not for the tin in the connecting cable, it would be almost impossible to discern where the cable begins and the connector begins after the swage.

Q.  Do current or pending standards allow for sparking grounding electrodes?

A.  ABYC TE4 allows for supplemental grounding conductors, as does the 2008 version of NFPA 760 Ch. 8.  These can have a water-contact area of less than 1 ft2, including zero.

HStripTM

Question

Answer

What is significant about an area of one square foot?

Not much

What do you recommend for the through-hull penetration?

Great caution

Why do you recommend 1/0 or 2 AWG cable whereas ABYC says #4 is adequate?

Less margin of error

Can I lower drag by embedding the strip flush with the hull?

To a point

Why should the ground strip be made of solid tinned copper?

Safety & reliability

Q.  What is significant about an area of one square foot?

A.  One square foot is a nice round number.  It turns out (see Concepts) that a typical lightning current flowing uniformly out of a 1 ft2 ground area immersed in salt water generates a fairly low voltage of about 11kV.  However, even in sea water sideflashes have caused hull damage when there was too large a distance between the mast and the grounding surface and the connecting cable was too close to the hull.  In fresh water the voltages generated are large enough to cause sideflashes from multiple conducting fittings.   As Thomson,1991 concludes "the 1 ft2 is shown to be hopelessly inadequate to prevent sideflashes in fresh water".  In fact, of more importance than the area is the shape of the grounding surface.  A square 1 ft2  plate has a grounding resistance of 0.36 ohm.  In contrast, our HStripTM with dimensions of 0.36" x 2" has only half the area but less resistance (0.29 ohm).  Also, if we split the traditional one square foot area into two strips, we can place each near the periphery of the boat to allow for externally-routed connections but still have a total area equal to that required in the standards.

Q.  What do you recommend for the through-hull penetration?

A.  Each  through hull penetration is a potential source of water leakage into the hull and, in a water soaked hull, the connection through the hull couples the lightning current into this hull moisture.  The result can be multiple blow outs from the hull moisture through the gel coat and into the water, where the extent of damage depends on the whim of the lightning.  Since the internal damage is invariably masked by the hull coating, it is very difficult to ascertain this.  So, for each hull penetration we recommend careful attention to the hole treatment to ensure as large a lay up of insulating and waterproof insulation between the hull and the connector.  We also use proprietary techniques in our connector design to minimize the risk of sparks forming from the connector.

Q.  Why do you recommend 1/0 or 2AWG cable whereas ABYC says #4 is adequate?

A.  Many years ago the recommended cable size for down conductors in standards was #8 AWG.  This changed after the publication of earlier scientific calculations of heating in cables in Thomson,1991 showing that a large lightning current could cause #8 copper cable to melt.  In addition, actual observations indicated failure of #8 gauge wire.  So #4AWG was chosen based on these heating curves.  However, other research performed by Dr. John Tobbias indicated that even #4 gauge copper shielding wire could rupture at large current owing to the magnetic pinch effect.  So we recommend 1/0 or 2 AWG gauge for all major connections.

Q.  Can I lower drag by embedding the strip flush with the hull?

A.  Since the sharp edges of the HStripTM are designed to form sparks, these should remain exposed.  However, 1 mm (.04") or so should be enough for this purpose.  So, yes, but leave about 1 mm protruding.

Q.  Why should the ground strip be made of solid tinned copper?

A.  With the price of copper heading into the stratosphere, a cheaper product could be made using sintering to introduce cavities into the metal.  Unfortunately, despite many opinions to the contrary, this does not lower the resistance when used as a lightning ground.  The scientific explanation comes directly from the definition of ground resistance

where the symbols have their conventional meaning.  The dot product in the denominator means that only the perpendicular component to the current density J contributes to the total current.  Merely increasing the total surface area of S does not increase the current I and has negligible effect on the electric field E.  So the resistance of a solid immersed conductor is theoretically the same as the resistance of one that has a pitted surface.  One very undesirable consequence of filling a grounding conductor with holes is that there is now less metal so that the resistance of the conductor itself is larger and hence it is more likely to heat up when lightning flows through it.  Add in the water that is inside the holes, and we now have the potential for some of the current to flow inside confined pockets of water.  It takes little imagination to work out what is likely to happen if this water reaches its boiling point. 

As for tinning, we tin plate all of our cuprous metals, including brass and bronze, to improve their corrosion resistance.  This is consistent with our philosophy to make all of our products to the highest possible standards.  And if we do not like the standards, we rewrite them! 

Common misconceptions & questions

Question

Answer

Reason

If I add a chimney brush to my mast I will not be struck

Wrong

Reputable scientists have much to say on this score.

A temporary "system" is adequate

No

It needs to be deployed first

What IS a lightning protection "system"?

Integrated

Many parts assembled together to minimize the risk of damage.

Liability is less if nothing is done

Wrong

A good lightning protection system  lowers the chance of injury.

A protection system just attracts lightning

No

Florida marine surveyors should know.

Can I reduce my insurance premium?

Not yet

A good LPS decreases the risk of injury & damage, but standards are needed. 

Lightning always takes the shortest path to ground.

Wrong

Tortuosity in lightning channels reflects how air breaks down in short spurts.

How do I protect a steel ship?

With care

Sideflashes through the hull are not a problem, but crew and electronics protection still is.

A temporary system is adequate?

First of all, it is difficult to conceive of any temporary measure that could be classified as a "system".  See the next question for more on this.  But a fundamental problem with any temporary measure, independent of its effectiveness, is well demonstrated by this  first hand account from Joe & Kathy Siudzinski's report of 27 October, 2003 , when they encountered some "Evening Unpleasantness".  The full account plus additional analysis is here. 

It's getting darker, and lightning starts appearing.
The wind drops off and eventually goes back to the north, but there is LOTS of lightning coming in from the west.
Using the radar, I pick out a big cell moving fast towards us and after plotting it I decide to go north to avoid it because there is a lot of lightning to the south. This works, barely, as all this horrible stuff passes a couple of miles behind us. Now, this isn't just inter-cloud lightning, this is huge massive bolts coming down and hitting the water!
We try to compare notes with the other two boats - even though we are very close, we can barely hear each other on either the VHF or SSB. Anyway, the boat in front goes south while we and the one behind us continue northwards. Big mistake.
To make a long story short, we spent eight hours surrounded by lightning and occasionally some incredibly heavy rain. Why we didn't get hit, I'll never know, because we repeatedly ended up right smack dab in the middle of the storm cells.
I was too chicken to go out there and install my home-made grounding rod (battery cable terminated in a copper water pipe which I strap onto the mast) as by the time I realized there was lightning it was too late.
I put our backup GPS, a compass, and a hand-held VHF into the BBQ (Faraday Cage). Should have put one of the computers in there also.
Kept the radar and engines going the whole time, the boat nicely steering itself on autopilot. Winds weren't too strong after the initial lashing, maybe up to 20. Kept the mainsail up and on the fourth reef and locked dead amidships with the two preventers and mainsheet.
This was one of the most awesome and spectacular events in my life - if we weren't right inside these humongous thunderstorms, I would have loved watching it. As it was, those sizzling bolts coming down into the water not far from the boat were the most fearsome things I've ever witnessed. This was continuous incessant lightning and not just a bolt here and there - it was daylight out there! The smell of ozone permeated the air. Would you believe I forgot that I now have a camcorder on board!
Anyway, I spent the time alternating between setting the engines and autopilot to what I thought would avoid the major upcoming nasties (totally unsuccessful in this) and then curling up next to Kathy on the bunk down below. A pillow over the head minimizes the flashing lights. I think we both got religion last night.
While in the middle of one of the last nasty chunks of thunderstorm that I failed to avoid, I bit the bullet and turned the boat south and after we got out of that one we were able to avoid the few remaining nasties.
It was over with by
2am .
At least the boat got washed.
The other two boats came through unscathed, but each caught with a man on deck stowing sails when the winds hit.
Kathy's doing fine, figuring it's just another strange ritual one goes through when sailing a boat across the ocean.

This reminds me (Ewen) of my first attempt at a lightning protection in my Mirage 5.5 on its maiden cruise to Cumberland Island , GA , in the height of the summer thunderstorm season in 1986.  It consisted of two large aluminum plates that I planned to throw over either side after wrapping the attached cable around the mast.  Of course, when we set off to explore the island in the morning under blue skies the precaution slipped my mind, and by the time we came back to shore the storm was already overhead and there was no way I was about to run around deck with long grounded cables in my hand.  One boat in the anchorage did get hit during that storm.  In addition to the risk of electrocution during attachment, there is also the problem of flailing underwater metal objects crashing against the hull.  A one-square foot immersed surface creates a considerable drag cross section!   Consequently, we advise against  temporary grounding systems.  Read the next answer for a discussion of the "system" part of this.

What IS a lightning protection "system"?

In the context of lightning protection, the word "system" can be reasonably interpreted using the definition  "a combination of interacting or interdependent components, assembled to carry out one or more functions".  The interacting components are the various parts  such as air terminals, main conductors, connectors, and grounding terminals, that are assembled, that is, installed and connected, to perform the function of minimizing the damaging effects of lightning.   There are several potentially damaging effects, such as heating, fire ignition, high voltage transients, sparks, electric and magnetic field interactions, hazardous voltage formation, etc., and an integrated protection system requires a sufficient number and distribution of all parts in order to accomplish its desired function of minimizing the probability of any damage. 

In concrete terms we consider a lightning protection system to have:
  • Air terminals distributed preferentially around the perimeter to give a zone of protection that covers the whole boat;
  • At least one conducting loop that encircles the living area, composed of main-sized conductor;
  • Adequately sized connections between conductors in the system;
  • Multiple grounding terminals distributed mainly around the waterline;
  • At least one square foot of immersed area in contact with the water at all times.

Since, in addition, our system is a lightning protection system for a boat, we need to add another set of requirements that are appropriate for any marine system, such as:

  • Corrosion resistant materials;
  • Galvanic compatibility at all joints;
  • Aesthetically acceptable.

Now reread the above question and mark off the deficiencies.

Liability is less if nothing is done?

There is a belief amongst some manufacturers that if they install a lightning protection system that then fails they are more liable than if they had done nothing at all.  There is no obligation to do this as standards are not mandatory and are intended mainly to improve personal safety, not to assure it.  However, there is solid evidence that even perfunctory adherence, such as grounding a mast to keel bolts, decreases damage.  Hence this argument would tend to fail the "due diligence" requirement. 

Gary Crist J.D. addresses this argument in "When lightning strikes" published in Golf Course Management,  pp. 21-22, April 1996 as follows: "Many people incorrectly believe that liability is best avoided by doing nothing.  Those who assert this illogical argument believe their approach disassociates them from the hazard, rendering them not responsible for any resulting damage or injury.  Such thinking is legally incorrect, to say nothing of its utter insensitivity."  While Dr. Crist was referring to lightning hazards on golf courses, the same reasoning applies to lightning protection of boats. 

Other legal points are raised by Krupnick et al. in "Lightning injuries: Electrical, medical and legal aspects" pp. 157-194, by Andrews, Copper, Darveniza and Mackerras (eds.) CRC Press, 1992.  Specifically, they point out on page 158 that although the phenomenon of lightning is beyond man's control and therefore correctly deemed an "Act of God",  when someone in a position of responsibility does not take reasonable measures to protect against injury and damage they may be held liable.  They state "It is generally held that if injury or damage results from the lightning strike and, concurrently, an act of negligence committed by a responsible person, such person cannot escape liability if the injury or damage would not have occurred except for the persons failure to exercise due care."

In the context of lightning and yachts, it would seem that a lightning protection system is a reasonable measure to take to insure the safety of all on board.  Perhaps the best argument against the do-nothing approach is that liability claims only follow after costly damage or injury and the best way to minimize the risk of these is to install the best system possible

A protection system just attracts lightning?

A common, and dangerous,  misconception is that an ungrounded mast is less likely to get struck than one that is grounded.  It is dangerous because this is frequently given as a good reason to leave a boat with no protection system.  The point was addressed in a University of Florida research project whose conclusion was a resounding "No" based on the experiences of marine surveyors:  grounding a sailboat mast does not cause an increased risk of a lightning strike".   Educational materials in the form of a pamphlet and video are available on line, and the section concerning grounding vs. no grounding is here.  Note that in this survey and its discussion in the pamphlet, "grounding" and "lightning protection" were synonymous.  Specifically, one of the  questions asked of the surveyors was "How many of these sailboats had a lightning grounding system, that is, had the base of their mast bonded to the keelbolts or a ground plate under the boat".

In fact, finding the answer to this question was one of the primary objectives of the University of Florida study.  Theoretical arguments without experimental data are of limited use because of the complexity and lack of understanding of the attachment process.  For example, recent work at New Mexico Tech indicates that the upward going streamer  is preceded by short (~microsecond duration) current pulses rather than  suddenly turning on.  And who could have predicted from theory that blunt lightning rods work much better than sharp ones? So we attempted to get some data by saturating the Lake Lanier and Lake Norman areas with posters requesting that we be notified if anyone was struck by lightning.  Unfortunately, no notifications came in.  So the surveyor's survey was the less-desirable alternative.  

However, if anyone has a strong desire to add a lightning protection system that is insulated from the water, the new NFPA standard allows for this possibility.  After considering the problems of both galvanic corrosion and, even worse, electrolysis in a marina where ground leakage currents are flowing in the water,  we included the provision for an air gap to break the circuit to any immersed grounding conductor.  This has the additional benefit of not introducing AC ground fault current into the water, which is a major cause of electrocutions.  The air gap should be within 8" of the grounding conductor and its breakdown voltage should be between 600V and 15kV.  Since  SiedarcTM grounding electrodes are preferentially placed above the waterline, this means that we can construct a NFPA-compliant system with multiple grounding points that is electrically isolated from the water.   See the Seminars page information about the NFPA standard. 

Can I reduce my insurance premium?

     An effective LPS lowers the risk of damage and decreases insurance claims in several ways:

     (1) In a well grounded and bonded system, the risk of personal injury, and therefore a liability claim, is decreased.   Cost/benefit ratios can be very small.  For example, the cabin space below a deck-mounted mast and above a keel bolt is at high risk of a connecting spark, a risk that can be virtually eliminated by adding a bulkhead below the mast and connecting the mast base vertically to the keel bolt.

     (2)  Although the survivability of electronics systems is extremely difficult to guarantee, a network of lightning conductors that surrounds the systems provides a good shield.  Also, measures such as common cable harnesses, twisted wire pairs,  and transient suppressors used, for example, in telecommunication facilities are likely to increase the chances.  A frequent problem is that all electronics systems are incapacitated, include the CDI system in outboard motors.  Any protection system that helps to ensure that key propulsion and control systems are functional after a lightning strike will decrease  the risk of both personal injury and loss of the boat.

     (3) According to Boat US  the cost of repair to a submerged boat is about 40% of the boat value.  Hence if a lightning strike blows out a through-hull transducer, the resulting hole could form the basis of a very expensive claim.  While the risk of this happening cannot be eliminated, appropriate protective measures can significantly lower this risk.  As an example, consider a fisherman with a metal superstructure surrounding the helm and the usual cluster of instruments.  Invariably the speedometer or fish finder is located in the hull directly below the instrument cluster and connected to it via narrow gauge wires.  A likely path for a lightning strike is down the VHF antenna into the instrument cluster, down the narrow gauge wire to the speedometer transducer, and into the water.  Since the transducer has not been designed with lightning in mind, a blow out is probable.

     The above reasons would appear to dictate an answer of "Yes" to the question "Can I reduce my insurance premium?"  In actuality, it is much more complicated as any premium reductions would need to be assessed according to guidelines relating risk abatement to lightning protection measures.  For example, a boat either has a carbon monoxide detector or it does not, but the same cannot be said of a LPS since each boat is different and the type and degree of protection depends on the individual boat type.   For example, in a small open boat the main concern is to avoid a direct lightning strike to a person, but in an offshore fisherman an equally pressing need is for survivability of propulsion and control.  To further complicate matters, a LPS should always be installed during manufacture but this adds costs that will probably not be recouped by the owner in reduced premiums.  On the other hand, the insurer also has the prerogative of raising deductibles and denying coverage and so can further influence the decision of the owners, and through them the OEM's, to demand adequate protection. 

Our dream ship is 55'-75' long and made of steel. If you were to own such a vessel, how would you protect it?

     A steel hull means that the risk of holes being blown through the hull present in fiberglass and wooden boats is virtually eliminated, although it is possible that a through-hull could still blow out or some damage to the hull surface could occur at the exit points.  Also, reports of damage to propellers and engine electronics may indicate that uncoated immersed fittings (propellers, bow and stern thrusters, unpainted thruhulls) provide preferred paths. Hence, even in a metal vessel it is advisable to add grounding strips outboard of these immersed fittings. We are still assessing the role of Siedarc electrodesTM in metal hulls. The remaining concerns are then protection of (i) crew, and; (ii) electronics.  Crew protection reduces to two further cases (a) direct strikes, and; (b) sideflashes

     (i) (a) Crew protection from direct strikes  The objective here is to ensure that lightning does not attach to any place on the deck, that is, where a crew member might be standing. As an illustration of an effective but extreme measure, NASA at Kennedy Space Center suspend a catenary wire above a sensitive installation, for example a launch gantry,  to intercept the lightning via an upward-going streamer and divert the lightning channel away from the gantry.   A similar technique can be used if a ship has multiple masts supporting a wire. 

     Vertical conductors afford some protection for  the surrounding area by attracting lightning attachment to their top, or, more accurately, by preferentially launching an upward-going streamer to intercept the downward-going leader.  This concept has been summed up in the term  "cone of protection".   However,  in practice the cone is rather leaky as it is based on probability rather than certainty - a better name for it would be the "sieve of protection"!   Hence nearby lightning rods lower the risk of nearby attachment, but do not eliminate it.  Much better protection is afforded inside metallic stays. In the case of a passage maker with a small aft mast the area inside the stays could be considered well protected, but almost no protection is offered outside this area.  Anchoring during a thunderstorm on this ship would be a hazardous occupation.  Note that the mechanism for lightning attachment is unaffected by the material used in the hull and whether the mast(s) are grounded or not. 

     (i) (b) Crew protection from side flashes  A sideflash is a spark that travels (usually) between the main lightning conductor and a nearby conductor - water (both in water tanks on the boat and the water it is floating in) and crew members both being considered conductors.  However, if the lightning attachment point, for example a mast, is not  connected  to a grounding conductor in the water  then a major sideflash may be more vertical than horizontal and carry a large proportion of the lightning current - several tens of kiloamps

     Sideflashes can also occur in a boat whose main lightning conductor IS well grounded.   As a result of the high voltage caused by the lightning current, discharges may form between the main conductor and any nearby conductors. Bonding  is the answer to this problem, but the bonded conductor is then raised to the voltage of the lightning and this needs to be taken into account.  Not that this is bad - birds can perch on high voltage lines without injury - but it may create problem areas near the water, which is closer to "ground" voltage, especially in fiberglass and wooden hulls.   In fact, in order to prevent sideflashes the whole boat needs to be raised to the potential of the lightning conductor.  This is much easier to do in a steel or aluminum ship since the whole hull can be incorporated into the bonding system. However, if the cabin and pilothouse are fiberglass or wood, separate conductors need to be added for the main down conductor system and the bonding system. When adding these care needs to be taken that the conductors do not cause galvanic corrosion of the hull.

     (b) Protection of electronics  Lightning damage to  electronics is a major problem since the combination of low-voltage equipment such as computers, remote transducers (e.g. weather instruments, radar, radio antennas), and close lightning is a very bad mix.  To make matters worse, a direct strike is not necessary - electronics can be blown from nearby lightning as a result of induced currents flowing off masts, etc.  Devices such as transient voltage protectors are designed to limit voltages entering electronic circuits and the incorporation of these on circuit boards significantly increases their chances of surviving a close or direct strike. In addition, equipment layout and the harnessing of interconnecting cables is crucial.   There are some fundamental principals that need to be followed to reduce the risk of damage, but it can never be reduced to zero.  As in all types of lightning protection, it is a case of improving the odds.  From my past work on sailboats,  the chance of damage to at least some electronics was more than 90%, and to all electronics,  40-70%.  A  "protected" boat in this study  was considered to be one with a grounded mast. This minimal level of protection improved the odds in fresh water, but there was no difference in salt water.  Hence  merely grounding the mast was not enough to improve the survivability of electronics.   I have no data on relative electronics damage in steel hulled ships.  From a theoretical point of view, a  fiberglass superstructure between a metallic mast and a steel hulled ship can be regarded as an insulating filling in a conducting sandwich.  If no precautions are taken, both the bottom of the mast and the top of the steel hull may simultaneously launch multiple sparks to complete the lightning's path to ground.